Unbalanced Voltage Compensation using Interfacing Converters in Hybrid AC/DC Microgrids Open Access

Descriptions

Other title
Subject/Keyword
Unbalanced Voltage Compensation
Power Electronics Interfacing Converters
Hybrid Microgrids
Type of item
Thesis
Degree grantor
University of Alberta
Author or creator
Nejabatkhah,Farzam
Supervisor and department
Yunwei (Ryan), Li (Electrical and Computer Engineering)
Examining committee member and department
Ali Khajehoddin (Electrical and Computer Engineering, University of Alberta)
Hao Liang (Electrical and Computer Engineering, University of Alberta)
Mojgan Daneshmand (Electrical and Computer Engineering, University of Alberta)
Yasser Abdel-Rady I. Mohamed (Electrical and Computer Engineering, University of Alberta)
Martin Ordonez (Electrical and Computer Engineering, University of British Columbia)
Department
Department of Electrical and Computer Engineering
Specialization
Energy Systems
Date accepted
2017-09-21T16:02:23Z
Graduation date
2017-11:Fall 2017
Degree
Doctor of Philosophy
Degree level
Doctoral
Abstract
Today, conventional power systems are evolving into modern smart grids, where interconnected microgrids may dominate the distribution system with high penetration of renewable energies and storage elements (SEs). The hybrid AC/DC systems with DC and AC sources/loads are considered to be the most likely future distribution or even transmission structures. For such hybrid AC/DC microgrids, control strategies are one of the most critical operation aspects. Also, unbalanced voltage caused by ever-increasing unbalanced distribution of single-phase/unbalanced loads, single-phase/unbalanced distributed generations (DGs), and remote grid faults has raised serious concern about such hybrid microgrids due to the adverse effects on the power system and equipment. In hybrid AC/DC microgrids, the high penetration level of power electronics interfacing converters creates great ancillary services potential such as unbalanced voltage compensation. These interfacing converters (IFCs) are the interfacing converters of DGs/SEs, and AC and DC-subsystems IFCs (they can also be called solid-state transformers). These IFCs can be single three-phase IFCs, parallel three-phase IFCs (when larger power and current capacity are needed), or single-phase IFCs. However, the operating interfacing converters under unbalanced voltage will introduce some adverse effects such as output power oscillations, DC link voltage oscillations (especially when the DC link capacitance is designed to be small for a three-phase converter), and the output peak current enhancement. Therefore, designing suitable control strategies for these IFCs for operation under unbalanced AC voltage or even to compensate for the voltage unbalance with consideration of the above adverse effects is very important. Moreover, since the compensation is realized through the available rating of IFCs, it is equally important to consider the effectiveness of the control strategy for unbalanced voltage compensation. The purpose of this research work is to develop control strategies for the interfacing converters for unbalanced voltage operation or compensation in hybrid AC/DC microgrids. Three interfacing converters configurations, single three-phase IFCs, parallel three-phase IFCs, and single-phase IFCs, are considered. Specifically, for single three-phase IFC control, the focus is on the minimization of adverse effects such as DC link voltage ripple and the effectiveness of the unbalanced compensation, while providing an adjustable level of unbalanced compensation ability. For parallel three-phase IFCs, which usually have the same DC link (the DC link of the DG, SE or the DC subsystem), since adverse effects can be multiplied by the number of IFCs, the control focus is to optimally utilize the parallel IFCs to minimize their adverse effects on each other. For this purpose, either one IFC can focus on the adverse effects minimization, or all IFCs can share it. For single-phase IFCs, the focus is to coordinate multiple IFCs to compensate the unbalanced condition while providing an adjustable level.
Language
English
DOI
doi:10.7939/R35X25S6R
Rights
This thesis is made available by the University of Alberta Libraries with permission of the copyright owner solely for the purpose of private, scholarly or scientific research. This thesis, or any portion thereof, may not otherwise be copied or reproduced without the written consent of the copyright owner, except to the extent permitted by Canadian copyright law.
Citation for previous publication

File Details

Date Uploaded
Date Modified
2017-09-21T22:02:23.607+00:00
Audit Status
Audits have not yet been run on this file.
Characterization
File format: pdf (PDF/X)
Mime type: application/pdf
File size: 7411748
Last modified: 2017:11:08 16:51:35-07:00
Filename: Nejabatkhah_Farzam_201709_PhD.pdf
Original checksum: 434ddf630b0b161fc23977412cdfc0a4
Activity of users you follow
User Activity Date